CAST IRON GATE VALVE 30CH6BR
Closing and opening of the 30ch6br gate valve is performed manually. Due to the progressive movement of the stem when turning the handwheel, the wedge rests against the support wall, pushing the disks apart. As a result, the sealing surfaces of the disks are pressed against the sealing surfaces of the body, ensuring the closure of the passage.
| No. | Product Name | Dimensions (DN) | Unit | Price (incl. VAT) | Origin |
|---|---|---|---|---|---|
| 1 | Cast iron gate valve 30ch6br | 150 | pcs | 1 sum | Russia |
Technical Specifications
| Specification | Value |
|---|---|
| Gate Valve | 30ch6br |
| Nominal Pressure PN, Bar | 10 |
| Working Medium | Water, steam |
| Type | Parallel double-disk |
| Body Material | Grey cast iron |
| Sealing Rings Material | Bronze / Brass |
Working Temperature, °C | up to 225 |
| Connection Type | Flanged |
| Operation | Manual with rising stem |
Maintenance
Operation of 30ch6br PN10 cast iron gate valves requires periodic visual inspection and maintenance, which includes:
Timely elimination of leaks in the gland and gasket connections by uniform tightening of the bolts.
Replacement of the gland packing.
In case of lack of gate tightness — cleaning the gate from deposits and lapping the seals.
Cleaning and lubrication of the stem.
Troubleshooting
| Malfunctions of 30ch6br | Possible Cause | Remedy |
|---|---|---|
| Tightness of the parallel double-disk gate is broken | The passage is not completely closed
Sealing surfaces are damaged or worn | Apply the calculated force to the handwheel
Lap or repair the defect |
| Leakage through gasket connections | Insufficient gasket sealing or loose bolt tension
The gasket is worn out | Tighten the bolts evenly
Replace |
| Gland leaks medium | Insufficient packing compression
Gland packing is worn out | Tighten the bolts
Add packing or replace with a new one |